TRUE RMS CURRENT AND VOLTMETER FOR AC AND DC
DM3430 Series

  • Accurate True RMS Reading
  • Galvanic Isolation To 3.5 kv
  • NEMA 4/IP65 Front Panel
  • Unique Option POD Design
  • Relay or 4-20mA Output Options
  • RS485 Serial Modbus
DM3400 Digtal Indicator

 

INTRODUCTION
The DM3430 is a true RMS current and voltage panel meter suitable for measuring AC or DC signals.  It has four digit, high intensity LED display that can be set to show a fixed number of decimal places with "auto-rounding" to always show the maximum resolution.

It is highly accurate and designed to measure AC or DC voltages up to 550 Volts or currents up to 6 Amps.  Readings can be displayed as current or voltage or, alternatively, the reading can be easily scaled from the front panel to take into account a multiplier from a transformed input or to display directly in engineering values.  The 3.5KV isolation gives added protection when the instrument is used to measure high voltages.  This is particularly important when measuring current, in that the instrument can be mounted anywhere in the measuring circuit and remains unaffected by any standing voltage.

The DM3430 has a number of special software features including Peak and Valley memory (Storing Maximum and Minimum readings) and an Alarm Inhibit that disables the alarm function for a programmable period after start up.  It is available with a choice of two power supplies, S1 for 90-253 VAC, or S2 for 20-35 VDC.

Output functions including dual relays, 4-20 mA retransmission or Modbus RS485 serial communications.  Options are all available and easily installed without dismantling the case thanks to the unique "plug and play" option pod design.

All programming is done via a simple to use menu accessible from the instrument front panel or via the RS-485 Modbus RTU serial communications option.

TRUE RMS EXAMPLE

The waveform shown is typical of that encountered in line voltage measurement with a fundamental plus 30% of 3rd harmonic. The 3430 will accurately measure this waveform while a scaled average meter could produce an error of 12%.


BENEFITS OF TRUE RMS MEASUREMENT

The DM3430 uses true Root Mean Square measurement.  This RMS value is related to the "heating effect" of a waveform i.e., the amount of heat that a signal would generate in a resistor (1 VAC RMS would generate the same amount of heat as 1 VDC).  This is quite different to the average or mean value of an AC signal, which is sometimes measured and then scaled as an RMS value.  This can be acceptable if the waveform is a pure undistorted sine wave.  Unfortunately this rarely occurs in practice.  Waveforms can vary considerably and therefore very significant errors of up to 30% for different waveform types can result as shown in the table below:

Wave Type Crest Factor
(V Peak/V RMS)
True RMS Mean Value
Calibrated to
read RMS
% Error in
Mean Circuit 1
.Pure Sine Wave 1.41 0.707 0.707 0%
.Symmetrical
.Square Wave
1 1 1.11 +11%
.Pure Triangle
.Wave
1.73 0.577 0.555 -3.8%
.SCR Waveforms
.50% Duty Cycle
.25% Duty Cycle
2
4.7
0.495
0.212
0.354
0.15
-28%
-30%

1 Error = (Mean Value + True RMS Value) / (True RMS Value) * 100%


THE IMPORTANCE OF ISOLATION

The input is galvanically isolated to 3.5 KV from the rest of the electronics circuitry. What this means in practice is that any standing voltages can be ignored and currents or voltage differentials can be measured with high levels of common mode potentials. The Common Mode Rejection Ratio is a measure of the amount of error introduced when common mode voltages exist. The DM3430 has an exceptional rejection ratio of 102 dB which means that even high levels of standing voltage have little or no effect on the overall measurement accuracy.

SPECIFICATION @ 68 °F

.INPUTS
 

.AC 1

.DC  
.Ranges 2 .Voltage .550
.60
.±550
.±60
.Volts
.Volts
.Current .6 .±6 .Amps
.Accuracy 3   .0.1% Rdg ±0.1 FSD .0.1% .FSD
.Stability 4   .0.02 .0.02 .% / °C
.Input Impedance .550 V Range
.60 V Range
.6 A Range
.10
.1
.0.02
.1
.0.02
.0.02
.M ohm
.M ohm
.ohm
.Frequency Range   .0 to 20 .N/A .K Hz
.Frequency Effect .20 Hz to 1 K Hz
.1 K Hz to 20 K Hz
.Negligible
.0.04
.N/A
.N/A
.% / K Hz
.% / K Hz

 

.GENERAL
.Isolation 5 .3.5 .3.5 .K Volts
.Display (with Auto-rounding) 6 .0 to 9999 .-999 to 9999 .Counts
.Resolution 7 .A/D
.Display
.0.002
.0.017
.0.002
.+ve 0.017
.-ve 0.17
.% FSD
.% FSD
.% FSD
.Reading Rate .3 .3 .Hz
.CMRR 8 .102 .102 .DB
.Power Supply .Switch Mode S1
.Switch Mode S2
.90 to 252
.20 to 35
.90 to 252
.20 to 35
.VAC
.VDC
 

NOTES:
1- Based on 50/60 Hz AC signal
2- All ranges have a 10% over-range capability
3- Crest factor is the ratio between the Peak voltage and the RMS voltage and can have an effect on accuracy as shown in the following table:

Crest Factor Degradation of
Accuracy %
1 0
2 0.5%
3 2.5%

4- Over ambient Range 32 to 140 °F
5- 3 way isolation between input, PSU and any outputs: IEC pollution class 2
6- The A/D resolution frequency exceeds the display resolution. Auto-rounding makes maximum use of the 4 digit display by reducing the displayed resolution if the measured parameter exceeds the available digits thus providing a level of performance in excess of the four digit capability, i.e. if the reading id showing 999.9 and the input increases by 0.1 the new reading will show 1000.
7- Perceived resolution increases with the level of filtering
8- Common Mode Rejection Ratio

ENVIRONMENTAL

.Sealing to PANEL .NEMA 4, IP65
.Ambient operating range .-22 to +140 °F
.Ambient storage temperature .-58 to +185 °F
.Ambient humidity range .10 to 90% RH non condensing


APPROVALS

.EMC .Emissions .BS EN 50081-1
.Susceptibility .BS EN 50082-2
.ELECTRICAL SAFETY .BS EN 61010-1, UL (pending)

 

OUTPUT OPTIONS
Plug and Play Option Pods

Simple plug in pre-calibrated units, no dismantling or calibration

..Pod-3000/02  Dual relay Alarm
..
Two independent line rated relay outputs (common connection)
.Contacts .2 x Changeover relays common wiper
.Ratings .AC .DC
.Maximum Load .5A @ 250 V .5A @ 30V
.Maximum Power .1250 VA .150 Watts
.Maximum Switching .253 Volts .125 Volts
.Electrical Life .100,000 operations at rated load
.Mechanical Life .50 million operations
.Termination
Standard... .5 way tension clamp connector
Optional... .Screw terminals

 

..Pod-3000/03  Isolated re-transmission
.Ranges .0 to 10 mA (Active or Passive)
.0 to 20 mA (Active or Passive)
.4 to 20 mA (Active or Passive)
.Minimum current output .0 mA
.Maximum current output .23 mA
.Accuracy .0.07% full scale
.Maximum Output load
.Active... .1 K ohm
.Passive... .[(V supply - 2) / 20] K ohms
.Maximum External Supply Voltage .30 V (Passive mode)
.Voltage effect .0.2 µA/V
.Ripple current .< 3 µA
.Isolation .500 VAC
.Stability .1 µA/°F
.Termination
Standard... .5 way tension clamp connector
Optional... .Screw terminals


COMMUNICATIONS

..Pod-3000/05  RS 485 Modbus Comms.
..
PC communication for configuration and mounting.
.Physical Layer .4 wire or 2 wire half duplex RS485
.Baud Rate software selectable .19,200 or 9,600
.Protocol .Modbus RTU format
.Isolation .500 VAC
.Maximum Fan out .32 units
.Termination
Standard... .5 way tension clamp connector
Optional... .Screw terminals
Optional... .Ribbon Cable - RC


SOFTWARE FEATURES

.INPUT MENU
.Type .550V, 60V, 6A
.Display resolution .0, 1, 2 and 3 dps. (with Auto rounding)
.Scale .Scale factor (Default 1)
.ACDC .AC or DC input
.Filter .Off, 2 Sec, 10 Sec, Adaptive

 

.OUTPUT MENU (relay if fitted)
.The following parameters may be set for each individual relay
.Alarm type .Off, High, Low, Test
.Setpoint .Setpoint in engineering units
.Hysterisis .Alarm Hysterisis in engineering units
.Alarm delay .Off, 2 Sec, 5 Sec, 10 Sec, 20 Sec, 1 min, 2 min, 4 min
.Latch .Off, On (latch reset from front panel)
.Invert operation .Off, On

 

OUTPUT MENU (Analog Re-transmission if fitted)
.Span .4-20, 0-20, 0-10 (Set output range to 4-20, 0-20 or 0-10mA)
.Rt. Lo .User Defined (Set low end of scale)
.Rt. Hi .User Defined (Set high end of scale)

 

OUTPUT MENU (Modbus Comms if fitted)
.Device No.
.Baud Rate
.Connections
.1 to 99
.19.2 Kb / 1.2 Kb
.2  wire / 4 wire

 

SYSTEM MENU
.List .Short menu, Full menu
.Clear enable .Off, On
.Setpoint enable .Off, On
.Alarm inhibit .Off, 2 Sec, 4 Sec, 10 Sec, 20 Sec, 1 min, 2 min, 4 min
.Passcode .4 digit passcode
(0000-Passcode disabled)
.Offset .User calibration offset in engineering units

Items in Italics are only available if the "full menu" option has been selected

DM3430 Instruction Manual  (available soon)


ORDER CODE

DM343(LED Option) / Power Option

.DM343 Basic Model Number
.LED Options .0 = RED LED version
.1 = GREEN LED version
.Power Options .S1 = 90 to 253 VAC 50/60 Hz
.S2 = 20 to 35 VDC


OPTIONS

.Pod-3000/02 .Dual Relay Output (2 per unit maximum)
.Pod-3000/03 .Isolated 4 to 20 mA re-transmission (1 per unit maximum)
.Pod-3000/05 .Isolated Modbus RS485 (1 per unit maximum)
.Pod-3000/05-RC .Ribbon cable option (Pod 3000/05 only)
.ACC001 .Pack of ten 5 way optional screw terminals

 