LOW
COST TEMPERATURE TRANSMITTER
SEM104
|
 |
- User
Re-Rangeable
- Low
Cost
- Pt100
Inputs
- T/C
Input K, T, or J
- EMC
Tested
|
|
INTRODUCTION
The SEM104 series
are low cost 4 to 20
mA temperature sensor
transmitters housed
in a head mount DIN
standard connector block.
Available for Pt100
or Thermocouple inputs
the SEM104 is
field rangeable if necessary
by solder links on the
printed circuit board
and the use of on board
SPAN and ZERO potentiometers.
The transmitters are
low cost devices available
in standard, factory
calibrated ranges and
can be re-ranged to
suit most industrial
and Building Management
applications. |
GENERAL SPECIFICATIONS @ 68
°F
| .Output |
.4
to 20 mA loop powered,
Max. 30 ma |
| .Loop
Supply |
.10
to 30 VDC reverse connection
protected |
| .Loop
Resistance |
.700
ohms @ 24 V |
| .Loop
Volts Sensitivity |
.0.05%/V |
| .Temperature
Stability |
.ZERO
drift = 0.01%/°F |
| .SPAN
= 0.002%/°F |
| .Ambient
Temperature |
.32
to 150 °F at 24 V supply
250 ohm load |
| .Ambient
RH |
.0
to 95% RH non condensing |
| .EMC
Compatibility |
.Emissions
= BS.EN 50081 |
| .Susceptibility
= BS.EN 50082 |
INPUTS
| .SEM104P
PLATINUM RESISTANCE
SENSOR |
| .Sensor |
.100
ohm - 3 wire - alpha
= 0.00385 ohms |
| .Accuracy |
.±0.4
°F plus +0.2% of reading |
| .Offset
adjustment |
.range
dependant |
| .Span
adjustment |
.76
°F to 932 °F |
| .SEM104K,
T or J THERMOCOUPLE
SENSOR (ISOLATED JUNCTION) |
| .Accuracy |
.±0.1%
FS plus cold junction
errors non-linearized |
| .Offset
adjustment |
.±200
°F, solder link &
potentiometer |
| .Span
adjustment |
.212
to 1832 °F |
| .Impedance |
.>1M
ohm |
| .Burn
Out |
.Upscale
standard, Downscale
by link |
| .Cold
Junction |
.Automatic
32 to 158 °F |
| |
.Accuracy
0.4 °F @ 68 °F, tracking
+0.02 °F/°F |
| .Thermocouple
Types |
.J
= Iron / Constantan |
| |
.T
= Chromel /
Constantan |
| |
.K
= Chromel /
Alumel |
STANDARD RANGES °F
| Range
°F |
SEM104P |
|
SEM104K |
SEM104T |
SEM104J |
| -40
to +140 |
|
|
* |
* |
* |
| -100
to +100 |
* |
|
|
* |
|
| 0
to 200 |
* |
|
* |
* |
* |
| 0
to 300 |
* |
|
* |
* |
* |
| 0
to 500 |
* |
|
* |
* |
* |
| 0
to 750 |
* |
|
* |
* |
* |
| 0
to 1000 |
* |
|
* |
|
* |
| 0
to 1500 |
* |
|
|
|
* |
STANDARD
RANGES °C
| Range
°C |
SEM104P |
|
SEM104K |
SEM104T |
SEM104J |
| -30
to +35 |
* |
|
|
|
|
| -25
to +75 |
* |
|
|
|
|
| 0
to 50 |
* |
|
|
|
|
| 0
to 100 |
* |
|
* |
* |
* |
| 0
to 150 |
* |
|
* |
* |
* |
| 0
to 200 |
* |
|
* |
* |
* |
| 0
to 250 |
* |
|
* |
* |
* |
| 0
to 400 |
* |
|
* |
* |
* |
| 0
to 500 |
* |
|
* |
|
* |
| 0
to 600 |
|
|
* |
|
|
| 0
to 800 |
|
|
* |
|
|
| 0
to 1000 |
|
|
* |
|
|
Other ranges can
be supplied factory set or they
can be configured by the use
of solder links on the SEM pcb.
Full details are supplied with
each transmitter.
SEM104P
Instruction Manual
SEM104TC
Instruction Manual
ORDER CODE
SEM104
/ SENSOR /
Lo RANGE / Hi
RANGE / °F or
°C
Example:
SEM104/K/0/200/F is
the code for an SEM104 with
type K thermocouple input with
4 to 20 ma output over the range
of 0 to 200 °F
Call
(713) 861-1100 for literature and pricing.
If you prefer to ask for information via
the internet, email info@sandelius.com.
© 2001 Sandelius Instruments, Inc.