DUAL CHANNEL RTD DIN RAIL
PUSH BUTTON TEMPERATURE TRANSMITTER SEM523P

  • Two Independent Channels
  • PUSH BUTTON Calibration
  • RTD Sensor Input
  • Drift Free Digital Linearization
  • Re-Rangeable Without A Computer
  • High Density Packaging

 

INTRODUCTION
The SEM523P is a dual channel DIN rail temperature transmitter which accepts common RTD sensors and converts them into a 4 to 20 mA linear output.  Since Zero and Span are set to conform to a particular sensor type, the sensor temperature co-efficient (0.00385, 0.00392 etc.) has little to no effect on accuracy.

The simple push of a button ranges and calibrates the SEM523P transmitter.  There is no need for jumpers, potentiometer adjustments or a computer.  Ease of re-ranging assures you will have the range you need in stock.

High accuracy, stability, and flexibility at a very attractive price make the SEM523P the transmitter of choice for many applications.  The SEM523P provides a level of performance superior to analog units at comparable price.

CALIBRATION PROCEDURE:

  1. Connect an RTD simulator/calibrator to the input and between 8 & 30 volts DC to the output of the SEM203P.
  2. Set the simulator to the desired temperature at 4 mA.  Press and HOLD the calibration button until the LED starts to blink.
  3. Set the simulator to the desired temperature at 20 mA.  Press the calibration button and release.  The LED continues blinking and then shuts off confirming that the unit is calibrated.

It's that simple and that fast.


GENERAL SPECIFICATIONS @ 68 °F

.Channels .2 Independent
.Channel 1 to 2 Isolation .500 VDC
.Terminals .Two part screw terminal with rising clamp
.Max. cable size 0.059 in2
.Warm-up Time .2 minutes to full accuracy
.EMC Compatibility .Emissions BS EN50081-1
.Susceptibility BS EN50081-2
.Ambient Temperature Range .0 to 70°C
.Ambient Humidity .0 to 95% (non condensing)
.Calibration Period .12 months to maintain published specifications
.Display .Red LED indicates program mode or
.out of range sensor

INPUT

.RTD Pt100 (Pt-500 and Pt-1000 Optional)
.Sensor .3-Wire Pt100
.(optional 3 wire Pt-500 or Pt-1000)
.Sensor Range .-328 to +1562 °F [18-390 ohms]
.Minimum Span .68 °F
.Lead Resistance .Maximum = 100 ohms/leg
.Effect = 0.072°F/ohm
.(excluding mismatch)
.Sample Rate .500 ms per Sample
.Accuracy .±0.18°F ±0.1% Rdg (-148 to +932°F)
.±0.36°F ±0.2% Rdg (-328 to +1562°F)
.Thermal Drift .Zero = ±0.01 °F/°F
.Span = 50 ppm

OUTPUT

.Output Range .4 to 20 mA (2 Wire Loop Powered)
.(Can be ranged 20 to 4 mA)
.Maximum Output Range .3.8 to 22 mA
.Supply voltage .8 to 30 VDC
.Accuracy .±5 µA
.Burnout .Up-Scale 22 mA (Down-Scale to order) *
.Thermal drift .Zero = ±0.067 µA/°F
.Span = ±0.16 µA/°F
.Response Time .500 ms to Reach 70% of Final Value
.Loop Resistance .700 ohms @ 24 VDC
.Ripple Rejection .±0.002 µA/V
.(Measured @ 50 Hz 1 Volt p-p)

ENCLOSURE

.Type .DIN Rail enclosure conforming to DIN 43 880

.Top...

.Color = Grey
.Material = Lexan
.Approval = UL94-VO (self extinguishing)

Base... 

.Color = Black
.Material = Noryl
.Approval = UL94-VO (self extinguishing)

SEM523P Instruction Manual

ORDER CODE

.Dual INPUT PT Sensor
.SEM523P-1 100 ohm RTD
.SEM523P-5 500 ohm RTD
.SEM523P-10 1000 ohm RTD
.Note: All units supplied with Upscale Burnout.  Contact sales office for Downscale versions.

Call (713) 861-1100 for literature and pricing. If you prefer to ask for information via the internet, email info@sandelius.com.

 

© 2001 Sandelius Instruments, Inc. - All Rights Reserved